| Primary Current Rating |
100 A, 200 A, 400 A, 600 A, 1,000 A, 2,000 A, or application-specific values |
Choose a primary rating equal to or slightly above the maximum continuous system current. Avoid excessive oversizing when measurement accuracy at low load is important. |
Confirm the system voltage, frequency, maximum fault current, continuous load, and expected minimum load before final selection. |
| Secondary Current Output |
1 A or 5 A analog secondary |
Select 1 A for longer cable runs or lower wiring losses. Select 5 A when existing meters, relays, or switchgear are designed for a 5 A input. |
The secondary output must match the connected instrument or protection relay. Do not connect a 1 A CT to a 5 A input unless the measuring system explicitly supports it. |
| Metering Accuracy Class |
Class 0.1, 0.2, 0.5, 1, or 3 |
Use Class 0.1 or 0.2 for high-accuracy revenue or precision energy measurement. Use Class 0.5 for general power monitoring. Use Class 1 or 3 for basic indication and less demanding measurement. |
The stated accuracy applies only within the specified current range, frequency, burden, and power factor conditions defined by the applicable standard and product datasheet. |
| Protection Accuracy Class |
5P10, 5P20, 10P10, 10P20, PX, and related protection classes |
Use 5P or 10P classes for overcurrent and earth-fault protection after checking the relay burden and required accuracy-limit factor. Use PX or equivalent special classes when protection studies require defined excitation or knee-point performance. |
Protection selection must be coordinated with relay settings, fault current, CT saturation limits, remanence requirements, and the complete secondary circuit. |
| Rated Burden |
2.5 VA, 5 VA, 10 VA, 15 VA, 20 VA, 30 VA, or higher |
Select a rated burden equal to or above the calculated connected burden, including meters, relays, terminals, and cable impedance. Avoid selecting a burden far above the actual load for precision metering. |
For a resistive secondary circuit, approximate burden as VA = I² × Z. At the same impedance, a 5 A circuit produces 25 times the wiring burden of a 1 A circuit. |
| Frequency |
50 Hz, 60 Hz, or a specified operating range |
Match the CT frequency rating to the power system. For variable-frequency or harmonic-rich applications, select a CT specifically tested for the required frequency range and waveform. |
A standard power-frequency CT should not be assumed to provide the same accuracy under significant distortion, harmonics, or frequencies outside its rated range. |
| Core Configuration |
Solid-core, split-core, or window-type |
Use solid-core designs for new installations where maximum accuracy and stability are required. Use split-core designs when conductors cannot be disconnected, provided their accuracy and installation conditions are suitable. |
Split-core CT accuracy can be affected by core mating, conductor position, installation torque, and air gaps. Follow the specified mounting procedure. |
| Insulation and System Voltage |
Low-voltage, medium-voltage, indoor, outdoor, resin-insulated, or oil-insulated designs |
Select insulation level, creepage distance, clearance, and enclosure type for the actual system voltage and installation environment. |
Verify insulation level, impulse withstand, pollution degree, altitude, ambient temperature, and indoor or outdoor suitability against applicable standards. |
| Environmental Conditions |
Indoor or outdoor; standard, humid, dusty, corrosive, or high-temperature locations |
Specify the required IP enclosure rating, ambient temperature range, humidity resistance, mechanical strength, and corrosion protection. |
The CT enclosure and terminal arrangement should be compatible with the switchboard, busbar, cable dimensions, and available installation space. |
| Applicable Standard |
IEC 61869-2, IEEE/ANSI C57.13, or the project-required national standard |
Choose the standard required by the project, utility, inspection authority, or protection and metering equipment specification. |
Do not compare accuracy classes from different standards without checking their definitions, test points, burden conditions, and rated performance requirements. |
| Safety and Installation |
Shorting terminals, test blocks, grounded secondary, shielded wiring, and lockable enclosures |
Provide an approved secondary shorting and isolation method, clearly identify polarity, and ground the secondary circuit at one designated point where required. |
Never leave an energized CT secondary open-circuited. Dangerous voltage can develop and may damage the CT or connected equipment. |